跳到主要内容

IEC 60870-5-104

Zeus 的 IEC104 模块面向电力远动、能源网关和站端数据采集场景。当前内置覆盖主站常用路径:STARTDT 启动、总召唤、单点命令,以及归一化、标度化、短浮点测量值和设点。

安装

dotnet add package Zeus.Communications
dotnet add package Zeus.Protocols.Iec104

IEC104 通常跑在 TCP 通道上。无硬件时可以先挂虚拟站:

var options = new Iec104Options { CommonAddress = 7 };
var memory = new Iec104StationMemory();
memory.SetSinglePoint(1, true);
memory.SetScaled(100, 253);
memory.SetShortFloat(200, 25.3);

await using var app = ZeusHost.Create(builder =>
{
builder.AddVirtualChannel("iec-link", new Iec104SlaveResponder(options, memory));
builder.AddIec104("station", "iec-link", options);
});

await app.StartAsync();
var station = app.Devices.Get<Iec104Device>("station");
var values = await station.InterrogateAsync();

换真实网关时,把通道换成 TCP:

builder.AddTcpClient("iec-link", "192.168.1.20", 2404);
builder.AddIec104("station", "iec-link", new Iec104Options { CommonAddress = 7 });

点表采集

builder.AddAcquisition(TimeSpan.FromMilliseconds(1000));
builder.AddIec104(
"station",
"iec-link",
new Iec104Options { CommonAddress = 7 },
points: map => map
.SinglePoint("running", 1)
.Scaled("temperature", 100, scale: 0.1)
.ShortFloat("pressure", 200));

采集循环会周期执行总召唤,并把匹配到的 IOA 发布到点表。Scaled 配置 scale: 0.1 时,线值 253 会发布为工程值 25.3

写回

builder.AddIec104(
"station",
"iec-link",
new Iec104Options { CommonAddress = 7 },
points: map => map
.SinglePoint("remoteSwitch", 1).Writable("remoteSwitch")
.Scaled("setpoint", 100, scale: 0.1).Writable("setpoint"));

await app.Points.WriteAsync("remoteSwitch", true);
await app.Points.WriteAsync("setpoint", 18.6);

SinglePoint 使用单点命令。NormalizedScaledShortFloat 分别使用对应设点命令;配置了 scale 的点会在写回前反向换算为线值。

JSON 配置

{
"channels": [
{ "name": "iec-link", "type": "tcp", "host": "192.168.1.20", "port": 2404 }
],
"devices": [
{
"name": "station",
"channel": "iec-link",
"type": "iec104",
"commonAddress": 7,
"points": [
{ "name": "running", "address": 1, "dataType": "single-point" },
{ "name": "temperature", "address": 100, "dataType": "scaled", "scale": 0.1 },
{ "name": "pressure", "address": 200, "dataType": "short-float" }
]
}
]
}

虚拟站配置可写成:

{ "name": "iec-link", "type": "virtual", "responder": "iec104", "commonAddress": 7 }

支持范围

类型方向Zeus 类型
M_SP_NA_1 / C_SC_NA_1采集 / 写回SinglePoint
M_ME_NA_1 / C_SE_NA_1采集 / 写回Normalized
M_ME_NB_1 / C_SE_NB_1采集 / 写回Scaled
M_ME_NC_1 / C_SE_NC_1采集 / 写回ShortFloat

如果现场需要时标 ASDU、双点命令、文件传输或平衡传输扩展,建议先用通道追踪确认对端实际帧,再扩展 Zeus.Protocols.Iec104